Dual Control Dosing/Injection TDS/Ec Controller Cic-152

After-sales Service: One Year
Warranty: One Year
Display: Digital
Appliance: Biochemistry
Portable: Non Portable
Certification: CE
Customization:
Diamond Member Since 2008

Suppliers with verified business licenses

Rating: 5.0/5
Trading Company

Basic Info.

Model NO.
CIC-152
Type
Conductivity Meter
Weight
0.7
Transport Package
Box
Specification
Dimensions: 7.2 X 7.2 X 11.1 cm (2.8 X 2.8 X 4.4 i
Trademark
hm
Origin
Qingdao, Shandong Province, China
HS Code
9027809900
Production Capacity
100000 Pieces/Month

Product Description

Dual Control Dosing/Injection TDS/Ec Controller Cic-152

FEATURES

*Monitors and controls dosing or injection systems.
*Large, bright tri-color L. E. D. Display.
*Two adjustable set points keep TDS levels within a range (maximum and minimum TDS/EC levels).
*Minimum and maximum control points will activate relay controls via switching dry contacts.
*The CIC-152 can control two different devices (e. G., a pump and a valve).
*Two alarms (maximum and minimum levels) can be set independently of the control points.
*Digital calibration.
*On-screen temperature display.
*On-screen range & control indicator lights (green, yellow or red)
*Installs easily in minutes.
*Includes one sensor probe (no extra cost)
*Protective cover also available (sold separately)
*Available with the NaCl conversion factor (model CIC-152-N) or the 442TM conversion factor (model CIC-152-4).

SPECIFICATIONS

TDS Range: 0 - 5000 ppm (CIC-152-N): 0 - 8500 ppm (CIC-152-4)
EC Range: 0 - 9999 µ S
Temperature Range: 1-80oC; 33-176oF
Accuracy: ± 2% (of the reading)
Resolution: 0.1 ppm (0-999); 1 ppm (1000-9999)
ATC: Yes (1 - 80 degrees Celsius)
Calibration: Digital (by push button)
Factory Calibration: 1413 µ S
Conversion Factor: CIC-152-N: NaCl (avg. 0.5); CIC-152-4: 442 (0.4-0.7)
Set Points: Adjustable by push button. Control Point 2: Maximum TDS Limit. Control Point 1: Lower TDS Level.
Relay Control: The unit will transmit an analog signal (simple switch) via open or closed contacts to a device (e. G. Pump/valve) when the ppm/µ S level reaches the maximum TDS/EC limit (Control Point 2) or the minimum TDS/EC limit (Control Point 1). The contacts are switched back to the normal position once the TDS returns to the acceptable range.
Relay Voltage: 5V (attached devices must have their own power supply)
Alarm: Two independent alarms (set by user)
Display: Bright 5/8" L. E. D. Display
Probe: 1/2" bushing (NPT), 3 meter (9.8 ft) shielded cable (model SP-1-PSC)
Power supply: AC 110V / AC 220V
Dimensions: 7.2 X 7.2 X 11.1 cm (2.8 X 2.8 X 4.4 in. )
Monitor Weight: 241 g (8.5 oz)
Total (Shipping) Weight: 610 g (1 lb 5.5 oz)

Dual Control Dosing/Injection TDS/Ec Controller Cic-152